Product Description
Documentation
Contacting conductivity sensor brochure
Contacting conductivity sensor manual
Contacting Conductivity Sensors measure conductivity of a solution via electrodes. They are ideal for use in cooling towers and boilers, reverse osmosis equipment, and other non-oily applications. A variety of cell constants are available to handle a range of conductivities.
Boiler Contacting Conductivity Sensors
These cell constant 1.0 sensors are designed for boilers with water up to 10,000 μS/cm and pressures up to 250 PSI, 16.7 atm). These inline sensors are constructed from stainless steel and PEEK.
For the W100, W900 and W600 series controllers, a cell constant 10.0 sensor is available designed for boilers with water up to 300,000 μS/cm (range varies with solution temperature, see brochure).
WebMaster controllers require active sensors. These sensors contain electronics to convert the sensor signal to a voltage that these controllers can read. W400 and W100 series controllers use passive sensors.
Performance specifications vary with the type of controller, refer to the controller brochure. Typical boiler temperatures are 0 to 205 °C, 32 to 401 °F.